Get ready for the Certificate of Qualification exam for Electrician, Construction and Maintenance (309A), the Ontario name for the Red Seal Construction Electrician trade. Practise on original multiple-choice questions weighted like the real exam, with worked solutions for every calculation.

Free test → pay $7.99 CAD → instant access + emailed link

100questions on the Red Seal exam
4 hourswriting time
70%to pass
4options per question

Free test: 10 questions

Try 10 free questions from all five areas of the exam: common skills and safety, services and distribution, wiring, motors and controls, and signalling systems. You will see the right answer and the working after each one.

What the 309A exam is

Electrician, Construction and Maintenance (trade code 309A) is a compulsory trade in Ontario under the Building Opportunities in the Skilled Trades Act, 2021. To work in the trade legally you must hold a Registered Training Agreement, a Provisional Certificate of Qualification or a Certificate of Qualification (C of Q), and appear on the Skilled Trades Ontario Public Register. The apprenticeship is set at 9,000 hours: 8,160 hours on the job and 840 hours of in-school training.

When you finish your apprenticeship, or are approved through a Trade Equivalency Assessment, you write the certifying exam. Passing it leads to your C of Q from Skilled Trades Ontario. In Ontario the trade is part of the Interprovincial Red Seal Program under the national title Construction Electrician, and the Red Seal exam is the national standard for the trade.

Part of the examWhat to expect
Questions100 multiple-choice questions on the Red Seal Construction Electrician exam, each worth one mark
OptionsFour choices, exactly one correct, with no trick questions
Writing timeFour hours
Pass mark70%
Supplied at the examA formula sheet, an acronym list, a calculator if needed, and code book information where required
LanguageEnglish or French in Ontario
If you do not passIn Ontario, a 30-day waiting period before you can rewrite, and the exam fee is paid again

The Red Seal program says about 5 to 15% of questions test knowledge and recall, 60 to 70% test procedures and application, and 20 to 30% test critical thinking, such as working through a calculation or a code problem. Always check your Authorization to Test letter for the details of your own sitting.

How the exam is weighted

Red Seal exam questions come from the Red Seal Occupational Standard for the trade. The standard is split into five major work activities, and the official exam breakdown gives each one a set number of questions. Our sections follow the same five activities, and our 100-question mock exams use the same weighting.

Major work activityRed Seal questionsWhat it covers
A. Common occupational skills11Safety, lockout, tools and test equipment, commissioning, mentoring
B. Generation, distribution and services28Services and metering, protection devices, bonding and grounding, transformers, generators, renewables, high voltage
C. Wiring systems30Raceways, conductors and cables, branch circuits, HVAC, electric heat, exit and emergency lighting, cathodic protection
D. Motors and control systems21Starters and controls, drives, motors, PLCs and automated controls
E. Signalling and communication systems10Fire alarm, communication cabling, security and integrated building controls

Calculations you should be fast at

The formula sheet you get on exam day lists the formulas, but it does not tell you which one to use. Practise until these feel automatic:

  • Ohm's law and power. E = I x R, P = E x I, P = I squared x R and P = E squared / R, including what happens when a heater runs below its rated voltage.
  • Three-phase. Line and phase values in wye and delta (the 1.73 factor), kVA, and true power with power factor.
  • Transformers. Turns ratio, full-load current, and available short-circuit current from percent impedance.
  • Motors. Synchronous speed from poles and frequency, slip, horsepower to watts, and current from efficiency and power factor.
  • Voltage drop and AC circuits. Two-wire and three-phase voltage drop, reactance, impedance and power factor.

Safety rules worth knowing cold

Ontario's construction projects regulation (O. Reg. 213/91) sets out who may do electrical work, how a power supply must be locked out and tagged, what goes on the tag, the minimum distances from overhead lines, and the rules for rubber gloves, extension cords and GFCI protection outdoors. The Occupational Health and Safety Act sets out your duties as a worker and your right to refuse unsafe work. Where a safety answer comes from a regulation, our explanation names the section.

How to prepare

Start with the official Red Seal self-assessment and the exam breakdown to find your weaker areas. Use the occupational standard, not only your college textbooks, because the exam covers the full scope of the trade across Canada. Then drill one section at a time here, read every explanation, and finish with full timed mocks of 100 questions in four hours. Aim to score well above 70% in practice so a few hard questions on the day do not sink you.

Aptitude Tests Canada is an independent practice platform. We are not affiliated with or endorsed by Skilled Trades Ontario, the Red Seal Program, the Electrical Safety Authority or the Government of Ontario. Our questions are original practice questions, not real exam questions, and they do not reproduce the Canadian Electrical Code.

Three worked examples

One question from different sections of the full pack, with the answer and explanation.

Common occupational skills

O. Reg. 213/91 lists what must appear on the tag placed on a disconnected power supply. Which of these is NOT on that list?

  1. Why the equipment was disconnected
  2. The name of the person who disconnected it
  3. The date it was disconnected
  4. The circuit's voltage and ampere rating
Answer: D, The circuit's voltage and ampere rating. O. Reg. 213/91, s. 190 (6) requires the tag to show why it was disconnected, who disconnected it, that person's employer and the date. The circuit rating is not one of the required items.
Generation, distribution and services

In a single-phase 120/240 V three-wire service, what voltage is measured between the two ungrounded (line) conductors?

  1. 120 V
  2. 208 V
  3. 240 V
  4. 0 V
Answer: C, 240 V. The two line conductors come from opposite ends of the centre-tapped transformer secondary, so they are 180 degrees apart: 120 V + 120 V = 240 V between them, and 120 V from each to the neutral.
Wiring systems

A 1,500 W heater is rated for 240 V. How much current does it draw at rated voltage?

  1. 12.5 A
  2. 6.25 A
  3. 3.13 A
  4. 0.16 A
Answer: B, 6.25 A. I = P / E = 1,500 W / 240 V = 6.25 A. Using 120 V by mistake would give 12.5 A.

Get the full 309A practice pack

The free test shows you the style. The full pack gives you 174 original questions across all five Red Seal work activities, timed 100-question mock exams weighted like the real exam and scored against the 70% pass mark, and a worked explanation for every answer. It works on your phone, tablet or computer, with 4 weeks of access.

Full access

$7.99 CAD

one-time payment, no subscription, nothing renews. Access for 4 weeks from purchase.

  • 174 original practice questions on electrical theory, calculations, services, wiring, motors, controls and fire alarm systems
  • Mock exams: 100 questions in 4 hours, weighted by the official Red Seal exam breakdown
  • Worked solutions for every calculation, with units, and the O. Reg. 213/91 or OHSA section behind every safety answer
  • Practise one work activity at a time to target your weak spots
  • Score breakdown by section after every attempt
  • Works on phone, tablet and computer, with 4 weeks of access
Payments coming soon

Visa · Mastercard · Amex · Apple Pay · Google Pay. Secure payment by Stripe.

Questions and answers

How many questions are on the 309A exam?

The Red Seal Construction Electrician exam has 100 multiple-choice questions, each with four options and one correct answer. The Red Seal program publishes how many questions come from each major work activity, and our mock exams follow that breakdown.

What is the pass mark for the Red Seal electrician exam?

The Red Seal exam pass mark is 70%, and the writing time is four hours.

What happens if I fail the 309A exam in Ontario?

Skilled Trades Ontario requires a 30-day waiting period before you can retake a certifying exam, and you pay the exam fee again before you rebook.

Do I get the Canadian Electrical Code during the exam?

The Red Seal program says reference material such as math formulas, an acronym list and code book information is provided if required. Check your Authorization to Test letter for what applies to your sitting.

Is 309A the same as Red Seal Construction Electrician?

Yes. Electrician, Construction and Maintenance is the Ontario title for the Red Seal trade of Construction Electrician. Other provinces use titles such as Construction Electrician or Electrician.

Do I need to renew my 309A Certificate of Qualification?

Yes. 309A is a compulsory trade, and Skilled Trades Ontario requires journeypersons in compulsory trades to renew their Certificate of Qualification each year for it to stay valid.

Are these the real 309A exam questions?

No. Red Seal does not publish its exam questions and warns against companies that claim to have them. Our questions are original, written from the Red Seal Occupational Standard topics, electrical theory and Ontario safety law.

Other practice tests

Sources (checked October 6, 2026): Red Seal: Construction Electrician · Red Seal: Construction Electrician exam information (breakdown, question types, formulas) · Red Seal: Exam Preparation Guide · Skilled Trades Ontario: Electrician, Construction and Maintenance · Skilled Trades Ontario: Exam scheduling · Skilled Trades Ontario: Certificate of Qualification · Building Opportunities in the Skilled Trades Act, 2021 · O. Reg. 213/91: Construction Projects · Occupational Health and Safety Act (Ontario) · O. Reg. 164/99: Electrical Safety Code